National Cables - Rating Factors |
|
|
|
National Cable manufactures and market heavy duty rugged Industrial and House Wiring Cables 250/440 Volts and 660/1100 Volts grade, 70 degree Celsius Temperature grade in (a) Single Core Unsheathed, Single Core Sheathed, Flat Twin, Flat Three Core Cables with or without ECC confirming to BS 2004/BS 6004 with Solid/ Strained Copper Conductor.
Rating Factors for Variation in Ground Temperature
Ground Temperature degree C |
15 |
20 |
25 |
30 |
35 |
40 |
45 |
Rating Factors |
1.17 |
1.12 |
1.06 |
1.00 |
0.94 |
0.87 |
0.79 |
Rating Factors for Variation in Ambient Air Temperature |
Air Temperature degree C |
25 |
30 |
35 |
40 |
45 |
Rating Factors |
1.25 |
1.16 |
1.09 |
1.00 |
0.90 |
Rating Factors for groups of twin and Multicore Cables Laid in Group in Horizontal Formation |
NO. Of Cables |
Rating Factors for Axial Spacing |
|
Touching |
15cm |
30cm |
45cm |
60cm |
2 cables |
0.79 |
0.82 |
0.87 |
0.90 |
0.91 |
3 cables |
0.69 |
0.75 |
0.79 |
0.83 |
0.86 |
4 cables |
0.62 |
0.69 |
0.74 |
0.79 |
0.82 |
6 cables |
0.54 |
0.61 |
0.69 |
0.75 |
0.78 |
8 cables |
0.50 |
0.57 |
0.66 |
0.72 |
0.76 |
Group Rating Factors For Circuits of two single core Cables, Side by Side Touching, Horizontal Variation, Laid Direct in Ground |
NO. Of Circuits |
Spacing (between Centers of Circuits) |
|
Touching |
15cm |
30cm |
45cm |
60cm |
2 |
0.79 |
0.86 |
0.91 |
0.93 |
0.95 |
3 |
0.69 |
0.78 |
0.84 |
0.88 |
0.91 |
4 |
0.64 |
0.73 |
0.81 |
0.86 |
0.88 |
6 |
0.56 |
0.67 |
0.77 |
0.83 |
0.87 |
8 |
0.51 |
0.65 |
0.75 |
0.82 |
0.86 |
Group Rating Factors for Circuits of three Signal Core Cables, Side by Side Touching, Horizontal Formation, Laid Direct IN Ground |
NO. Of Circuits |
Spacing (between Centers of Circuits) |
|
Touching |
15cm |
30cm |
45cm |
60cm |
2 |
0.78 |
0.81 |
0.85 |
0.88 |
0.90 |
3 |
0.68 |
0.71 |
0.77 |
0.76 |
0.79 |
4 |
0.61 |
0.65 |
0.72 |
0.76 |
0.79 |
6 |
0.53 |
0.58 |
0.60 |
0.71 |
0.76 |
8 |
0.48 |
0.54 |
0.62 |
0.67 |
0.72 |
Rating Factors for Variation in Depth Of Laying In Ground |
Voltage |
Depth of Laying(cms) |
75 |
90 |
105 |
120 |
150 |
180 & above |
|
Rating Factor upto 12sq.mm |
1.00 |
0.99 |
0.98 |
0.97 |
0.96 |
0.95 |
1.1 Kv |
Rating Factor upto 12sq.mm & upto 300 sq.mm |
1.00 |
0.98 |
0.97 |
0.96 |
0.94 |
0.93 |
|
|
|